[–] [email protected] 19 points 2 months ago (1 children)

I looked up on google at one point what the minimum required depth for a cable running under a building is by NEC code. It told me it was 0 inches. I laughed and called it stupid, wtf do you mean 0 inches?? Upon further research, 0 inches is the correct answer, I felt real stupid after that -_-

[–] [email protected] 5 points 2 months ago (2 children)

Seems like a depth of 0 inches means you can just lay it on the floor?

[–] [email protected] 12 points 2 months ago (1 children)

No, it means 50% of the cable must be submerged or buried. Little speed bumps all around.

[–] [email protected] 4 points 2 months ago* (last edited 2 months ago)

The 0 inches is to the top of the cable or raceway used, so it would be have to be at least perfectly flush with the ground. Obviously you can go lower.

[–] [email protected] 5 points 2 months ago

As mentioned with the other guy, 0 inches is the requirement to the top of the cable or raceway used. So at minimum, you're allowed to be perfectly flush with the ground. Obviously you can and likely would go a little lower, although I don't have any experience with trenching myself.